国产AV一区二区三区亚洲_成人毛片18女人毛片免费看借种_国产在线视频欧美日韩_久久嫩草影院网站_Jizz国产一区二区_欧洲女人性开放视频首页_女人被又黑又粗猛进猛出_欧美孕交alscan巨交xxx_搪瓷管空气预热器_手机A级韩国乱理伦片在线观看

PRODUCT

PRODUCT

SMALL COMPACT THERMOSTAT
  • SMALL COMPACT THERMOSTAT
  • SMALL COMPACT THERMOSTAT
  • SMALL COMPACT THERMOSTAT
  • SMALL COMPACT THERMOSTAT
SMALL COMPACT THERMOSTAT

KTO 111 / KTS 111

Applies to: The mechanical thermostats KTO 111 and KTS 111 are two state regulators for use up to 5,000 meters in altitude, thanks to optimised air gap and increased creepage distance. By use of Push-In terminals the thermostat is wired tool-free. The Push-In terminals provide constant pressure on the wires to prevent them from coming loose (e.g. during transport). KTO 111: Thermostat (NC); contact breaker for regulating heaters. The contact opens when temperature is rising. KTS 111: Thermostat (NO); contact maker for regulating of filter fans and heat

download
  • > Safe wiring with Push-In connection terminal 

  • Faster and tool-free wiring 

  • Improved air intakes for ventilation

  • Easy adjustability of switch temperature setting 

  • for use in up to 5,000 m altitude  

The mechanical thermostats KTO 111 and KTS 111 are two state regulators for use up to 5,000 meters in altitude, thanks to optimised air gap and increased creepage distance. By use of Push-In terminals the thermostat is wired tool-free. The Push-In terminals provide constant pressure on the wires to prevent them from coming loose (e.g. during transport).  

KTO 111: Thermostat (NC); contact breaker for regulating heaters. The contact opens when temperature is rising.

KTS  111: Thermostat (NO); contact maker for regulating of filter fans and heat exchangers or for switching signal devises when temperature limit has been exceeded. The contact closes when temperature is rising.

TECHNICAL DRAWING



Small Compact Thermostat KTO 111 / KTS 111 Series





Setting range
Art. No.
Contact breaker (NC)
Art. No.
Contact maker (NO)
Switching
current2/
AC 250 V
Switching
capacity 
AC 120 V
max.
DC 24-72 V

Approvals
0 to +60 °C11100.0-0011101.0-0010 (2) A15 (2) A30 WVDEUL File No. E164102EAC
-10 to +50 °C11100.0-0111101.0-0110 (2) A15 (2) A30 WVDEUL File No. E164102EAC
+20 to +80 °C11100.0-0211101.0-023 (2) A3 (2) A30 WVDEUL File No. E164102EAC 
+32 to +140 °F11100.9-0011101.9-0010 (2) A15 (2) A30 WVDEUL File No. E164102EAC
+14 to +122 °F11100.9-0111101.9-0110 (2) A15 (2) A30 WVDEUL File No. E164102EAC


TECHNICAL DATA


Switch temperature difference7 K (±4 K tolerance)
Sensor elementthermostatic bimetal
Contact typesnap-action contact
Service life100,000 cycles verified
Max. operating voltage, frequency rangeAC 250 V, 50-60 Hz
Max. inrush currentAC 16 A for 10 sec.
Connection12 Push-In clamps
rigid wire 2.5 mm2 (AWG 14)
stranded wire1 1.5 mm2 (AWG 16)
Mountingclip for 35 mm DIN rail, EN 60715
Casingplastic according to UL94 V-0, light grey
Dimensions60 x 33 x 41 mm
Weightapprox. 40 g
Fitting positionvariable
Operating/Storage temperature-45 to +80 °C (-49 to +176 °F)
Operating/Storage humiditymax. 90 % RH (non-condensing)
Protection type/Protection classIP20 / II
Overvoltage category/AltitudeII: up to 5,000 m; III: up to 2,000 m

1 Stripped length of rigid wire: 10 to 12 mm. When connecting with wires, wire end ferrules must be used (square or trapezoid crimp). Length of wire end ferrule: 10 mm or 12 mm.

Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.

2 The level of switching current has an influence on the tolerance accuracy;